nVent ERICO

Load Cell Protector

FEATURES

  • Six wires and shield protection works with four or six wire systems
  • Suitable for compression or tension cells
  • Low series impedance, loadcells do not need recalibration
  • NEMA®-12 (IP-55) rated, suitable for outdoor use
  • Helps protect against excitation over-voltage and prevent loadcell damage

SPECIFICATIONS

Part Number LCP01A
Article Number 701610
Max Discharge Current (Imax), Shield to Ground 10 kA 8/20 μs
Max Discharge Current (Imax), Signal to Shield 0.3 kA 8/20 μs
Voltage Protection Level (Up), Shield to Ground 90 V
Voltage Protection Level (Up), Signal to Shield 30 V
Voltage Protection Level (Up), Signal to Signal 15 V
Loop Resistance 0.3 Ω
Technology Silicon Avalanche Diode (SAD)
Material Acrylonitrile Butadiene Styrene
Enclosure Rating NEMA® 12 (IP55)
Depth (D) 110 mm
Height (H) 56 mm
Width (W) 75 mm
Unit Weight 0.25 kg
Temperature -40 to 80 °C

Documents

Download PDF